Wiring your 8720sm motor power, Determining conduit box orientation, Wiring your motor power – Rockwell Automation 8720SM High Performance AC Induction Motors User Manual

Page 9

Advertising
background image

Publication 8720SM-IN001A-EN-P — February 2003

8720SM High Performance AC Induction Motors

9

Wiring Your 8720SM Motor
Power

The procedures in this section assume you have installed your 8720SM
motor correctly. This section includes:

determining conduit box orientation

wiring your motor power

determining your feedback connections

verifying thermal protector (thermostat leads) connections

Determining Conduit Box Orientation

The standard conduit box location for totally enclosed motors is top
mounted for left or right conduit entry without motor disassembly.
The 8720SM motors allow rotation of the conduit box in 90 degree
increments for lead outlet at front, back, or sides.

Wiring Your Motor Power

To wire your 8720SM three-phase motor power:

1. Bring 4 wire shielded Beldon VFD cable or equal to these

connections. For applications above 130A, use thick insulation
lead wire such as RHW-2 or equal and thread the wires through a
single grounded metal conduit.

8720SM Motor:

8720MC Drive (TB1 terminal):

U (T1)

U

V (T2)

V

W (T3)

W

Shield

Clamp

Advertising