Rockwell Automation 2706-LV2xX, -LV4xX Dataliner DL40 Plus Message Display Installation User Manual

Installation

Advertising
background image

Installation

Dataliner DL40 Plus Message Display
(Catalog No. 2706-LV2xX, -LV4xX)

Overview

This document describes how to install a Dataliner DL40 Plus display
(standard or slave version) and contains these topics:

Wiring and safety guidelines

Mounting and dimensions

Power connections

DIP switch settings

Specifications

For additional information, refer to:

DL40 Plus Message Display User Manual (Publication 2706-6.1)

DL40 Plus Slave Display User Manual (Publication 2706-6.3)

Wiring and Safety Guidelines

Install the DL40 Plus display conforming to NFPA 70E, Electrical Safety
Requirements for Employee Workplaces. In addition to the NFPA general
guidelines, refer to the following:

Careful cable routing helps minimize electrical noise. Route incoming
power to the module by a separate path from the communication cables.

Do not run communications wiring and power wiring in the same
conduit!

Where communication and wire paths must cross, make their intersection
perpendicular.

Grounding helps limit the effects of noise due to electromagnetic
interference (EMI). To avoid problems caused by EMI, properly ground all
equipment and use shielded cables.

Important: Power, input and output (I/O) wiring must be in accordance
with Class I, Division 2 wiring methods [Article 501-4(b) of the National
Electrical Code, NFPA70] and in accordance with the local authority having
jurisdiction.