Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
DIP Switch Settings
(Parallel Port Versions)
Two DIP switch banks are located on the back of the module. You can
access the DIP switches through a cutout, as shown below. Set DIP
switches using a thin nonconductive object. Do not use a pencil (broken
graphite pieces may short out the internal circuitry).
For details on DIP switch settings, refer to the DL40 Plus User Manual
(Publication No. 2706-6.1).
Switch Bank #1 (SW-1) controls: Debug Mode, Fast Reset Sequence,
Keyboard Type, Select Enable.
Switch Bank #2 (SW-2) sets the serial address. The serial address refers
to the address used for triggers received from the serial RS-485 port or
computer keyboard.
Important: Remove power from the DL40 Plus before setting any switch
except Select Enable, SW1-9. Select Enable can be changed with the power
ON. Switch settings are scanned only on power-up. The new setting for
Select Enable takes effect immediately. The new settings for all other
switches take effect when you power-up or reset the DL40 Plus.