Rockwell Automation 2090-UCSR-P900 900 Watt Passive Shunt Module Installation User Manual
900 watt passive shunt module, Installation instructions
 
1
Publication 2090-IN001A-EN-P — March 2001
Installation Instructions
900 Watt Passive Shunt Module
Ultra Series drives and controllers can require external power 
dissipation when large inertial loads are present. To ensure that drive 
faults due to excessive bus voltage do not occur, loads requiring 
power dissipation that exceed a drive’s internal shunt capability 
require the use of external shunt resistor(s). 
The passive shunt (Catalog No. 1398-SR9PF or 2090-UCSR-P900) can 
be used with the following products:
As a motor decelerates, power is returned from the motor to the drive 
module, causing the bus voltage on the drive to increase. Ultra servo 
amplifier products have circuitry that senses the voltage on the drive’s 
DC bus and dissipates power when needed. When the bus voltage 
reaches the shunt turn-on voltage of the drive, the internal shunt 
circuitry allows the excessive regenerated power to be dissipated 
through an external resistor. After the bus voltage is reduced to the 
turn-off voltage level, the shunt transistor turns-off and no additional 
power is dissipated by the shunt resistor. 
Drive
Catalog No.
ULTRA 200 Drives
1398-DDM-075, -075X, -150, and -150X
ULTRA Plus Drives
1398-PDM-075 and 1398-PDM-150B
Ultra3000 Drives
2098-DSD-075, -075-SE, -075-DN, -075X, -075X-DN, -150, 
-150-SE, -150-DN, -150X, and -150X-DN 
Ultra5000 Drives
2098-IPD-075, -075-DN, -150, and -150-DN
ATTENTION
!
Using the passive shunt with modules not listed can 
cause equipment damage or personal injury. 
Document Outline
- 900 Watt Passive Shunt Module
- Front Cover
- Installing the Shunt
- Product Specifications
- Back Cover