Connecting to the Shunt Terminal Block
1. Locate the external shunt terminal block (TB2) on your drive.
2.
E
nsure there is no power applied to the drive.
3. Remove the jumper installed between terminals 1 and 2 of TB2.
4. Connect the lead wires to terminals 1 and 3 of TB2. Tighten screws
to 1.25 Nm (11 in-lbs).
5. Gently pull on each wire to make sure it does not release from its
terminal.
6. Re-insert and tighten any loose wires.
7. Open the front door of the passive shunt.
8. Connect the lead wires to terminal block inside front cover.
Polarity is not important. Tighten screws to 2.25 Nm (20 in-lb).
9. Close and secure cover of shunt module.
Insert wires