Remote Keyswitch and RS-232 Assembly
Installation Data
3
Figure 3
Cutout Dimensions
CL
CL
20159a
2.625”
(66.7 mm)
2.625”
(66.7 mm)
3/16”
4 Places
3.000”
+0.025”
–0.000
∅
76.2 mm
+0.025”
–0.000
(
)
2. Install the assembly in the cutout, from the rear of the panel.
3. Use the washers provided between the screw heads and the front side of
the panel. The narrow end of the washer is oriented towards the head of
the screw, as illustrated in Figure 1.
4. Fasten the housing to the panel door with the four mounting screws
provided. To maintain a good seal, torque the screws down to between 9
and 12 inch-pounds.
5. Before installing the lower left mounting screw, thread the screw
through the end of the restraining chain attached to the cap. Then install
the screw in the housing.
6. Connect the RS-232 connector on the assembly to the RS-232 serial
interface port on the rear of the PanelView terminal (Figure 4). Attach it
with the mounting screws on the connector housing.
Figure 4
RS-232 Serial Interface Port on the Back of the Terminal
23745
CONFIGURE
RUN
RUN
CONFIGURE
RS–232 Serial Interface
RS-232 Serial Interface
Mode Select Keyswitch