Wire the adapter – Rockwell Automation 1797-ACNR15 ControlNet Ex Redundant Media Adapter User Manual
Page 14

14 ControlNet Ex Redundant Media Adapter
Publication
1797-5.14 - March 2010
Wire the Adapter
1. Connect the ControlNet Ex tap drop cable to connector, terminal A
after removing the insulator boot.
2. Connect the redundant ControlNet Ex tap drop cable to connector B
after removing the insulator boot.
ATTENTION
When connecting wiring, torque terminal screws to 0.8 to 1 Nm
(5 to 7 lb-in).
WARNING
Make certain that you power this adapter with an intrinsically
safe power supply. Do not exceed the values listed in the
specifications for this adapter.
If you connect or disconnect wiring while the field-side power is
on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed
or the area is nonhazardous before proceeding.
IMPORTANT
The tap drop BNC must also have its insulator ring in position
when inserted.
IMPORTANT
The tap drop BNC must also have its insulator ring in position
when inserted.
Only remove the BNC covers if the ControlNet Ex tap drop
cable is installed.
PWR
1797-ACNR15
3 2
A
B
G
C
E
D
F
41411