Rockwell Automation 2030-RLS_ _D Dual Remote Lockout Station User Manual

Dual remote lockout station, Cat. no. 2030-rlsxxd)

Advertising
background image

Dual Remote Lockout Station

(Cat. No. 2030-RLSxxD)

1

4

DUAL REMOTE LOCKOUT STATION

INSTALLATION INSTRUCTION SHEET

1

1013449

42052-125

OF

N/A

N/A

N/A

REVISION

AUTHORIZATION

DR.

CHKD.

APPD.

DATE

DATE

DATE

E - DOC

LOCATION: MILWAUKEE, WISCONSIN U.S.A.

B-vertical.ai

DWG.

SIZE

SHEET

B

1

2

3

4

5

6

7

8

A

B

C

D

E

F

G

H

REFERENCE

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

.XX:

.XXX:

ANGLES:

42052

G. Ushakow

5-08-06

5-08-06

5-08-06

M. Jutz

M. Scharnick

Figure 1
Dual RLS Enclosure Mounting
Flange Hole Dimensions

Overview

The Dual Remote Lockout Station (RLS) is a rotary operated, enclosed switch with two System Isolated verification lights
and an operating handle that can be locked in the OFF position to provide Lockout / Tagout. The Dual Remote Lockout
Station is used to initiate the isolation sequence simultaneously in two separate ElectroGuard® units by sending signals to
each control module.

The Dual Remote Lockout Station is an integral part of the ElectroGuard® Safety Isolation Systems manufactured by
Rockwell Automation and designed for use with only these systems.

Installing the Dual Remote Lockout Station

Install the Dual RLS in the vertical plane using the four mounting holes in the enclosure external mounting flanges (see
Figure 1) and refer to Pre-Installation Precautions on page 2-1 of the ElectroGuard® User Manual.

Dual RLSs should be installed at locations requiring access or exposure to two machines or processes simultaneously.
Proper positioning of Dual RLSs permits operators and/or maintenance personnel to easily initiate isolation in both
machines or processes after normal stopping means for each machine or process have been used.

ATTENTION: This device is a component of the ElectroGuard® Safety Isolation System. Altering, defeating or
bypassing any module or component of the Safety Isolation System may result in personal injury, death, property damage,
or economic loss. Only qualified service technicians must perform service or maintenance. Resealing of the device is the
responsibility of the person or organization performing the service or maintenance.

Specifications

6.00

(152.4)

10.75

(273.1)

(4) - Ø0.31 (7.9) Dia.
Mounting Holes

Description Specification

Dimensions H x W x D

11.5 in x 9.31 in x 7.97 in

(292 mm x 236 mm x 202 mm)

A = NEMA Type 1 / IP40

J = NEMA Type 12 / IP65

F = NEMA Type 4 / IP66

Degree of Protection
(By enclosure type designator)

C = NEMA Type 4X / IP66

Input Voltage Rating

24V DC (Supplied from Control Module)

Indicator Lamp

24V LED

Indicator Lamp Color Designator

W = white; G = green

#22 -14 AWG

0.5 -2.5 mm

2

Terminal Block - Wire Size
- Torque

4.2 – 4.6 lb-in.

0.5 Nm

Operating Ambient Temperature

0…+40B

C (+32…+104B

F)

Storage Ambient Temperature

-10…+60B C (+14…140B F)

Storage Relative Humidity

5…95%, non-condensing

Agency Certification

UL, cUL, TUV EN954-1 Category 4,
TUV EN60204-1