E - doc – Rockwell Automation 2030-RLS_ _D Dual Remote Lockout Station User Manual

Page 4

Advertising
background image

DUAL REMOTE LOCKOUT STATION

INSTALLATION INSTRUCTION SHEET

Figure 5
Wiring from the RLS Terminal
Block to a Connector Plug on a
Control Module or Expansion
Module

1

1013449

42052-125

OF

N/A

N/A

N/A

REVISION

AUTHORIZATION

DR.

CHKD.

APPD.

DATE

DATE

DATE

E - DOC

LOCATION: MILWAUKEE, WISCONSIN U.S.A.

B-vertical.ai

DWG.

SIZE

SHEET

B

1

2

3

4

5

6

7

8

A

B

C

D

E

F

G

H

REFERENCE

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

.XX:

.XXX:

ANGLES:

42052

---------------

----------
----------

----------

---------------

---------------

4

4

Remote Lockout Station Cable Specifications (Cont'd)

Table 3
Continuity Check Table

Remote Lockout

Station Status

Control Module / Expansion Module

Connector Plug

Connection Point Numbers

Continuity

ON 2

&

7

Yes

ON 3

&

8

Yes

ON 4

&

9

Yes

ON 1

&

6

No

OFF

2 & 7

No

OFF

3 & 8

No

OFF

4 & 9

No

OFF

1 & 6

Yes

1

1

The “System Isolated” light on the front of the RLS has an impedance of about 2K Ohms.

4. Wire each terminal block to its corresponding plug using appropriate cable (see Figure 5, also use Table 1 if using recommended cable).
The wires from the first connected ElectroGuard® system must go to one terminal block, and the wires from the second system must go to
the remaining terminal block.

5. Have one technician operate the Dual RLS while a second technician checks the continuity between connection points on the RLS
connector plug for the Control Module or Expansion Module of the first ElectroGuard® System (per Table 3). If continuity check is
unsatisfactory, review wiring in step 4 for errors and then re-check continuity. When all of the connections between the Dual RLS and the
first ElectroGuard® System are satisfactory, repeat for all connections between the Dual RLS and the second ElectroGuard® System.

6. When both continuity checks are successfully completed, close the Dual RLS enclosure cover, place the cover clamps over the lip on the
edge of the cover and tighten the two cover clamp screws.

7. Commission the unit per Chapter 3 of the ElectroGuard® User Manual Revision 2030-UM003A-EN-P or later.

To Control or Expansion Module

(RLS1 to RLS6) or (RLS_A to RLS_J)

RLS Connector Plug
For Connecting RLS to Control
Module or Expansion Module

Drain Wire

The fifth terminal of the
Connector Plug is not used
for RLS connection

Braided Cable Shield

Terminal Block
Inside Remote
Lockout Station

Color Coded
Cable Recommended

RLS Connector Port
Terminals in Control
Module or Expansion
Module

1 2 3 4

6 7 8 9

G
N
D

1 2 3 4

5 6 7 8 9

1
0

G
N
D

42052-125-01 (1)

Printed in U.S.A.

PART

NO.

MATERIAL

CHG.

LTR.

SIZE

FLAT

FOLD

-01

1

TWO SIDES PRINTED

17" W x 11" H

BODY STOCK WHITE

BODY INK BLACK

4-1/4" W x 2-3/4" H

THIS DRAWING IS THE PROPERTY OF

ROCKWELL AUTOMATION, INC.

OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,

USED OR DISCLOSED FOR ANY PURPOSE

EXCEPT AS AUTHORIZED IN WRITING BY

ROCKWELL AUTOMATION, INC.

Advertising