Connect external wiring – Rockwell Automation 1798-PFTP1 FlexArmor PROFIBUS Field Termination Plug User Manual

Page 5

Advertising
background image

FlexArmor PROFIBUS Field Termination Plug 5

Publication 1798-IN005B-EN-P - April 2002

2. Screw down the module retaining screws to ensure IP67

compliance.

Connect External Wiring

Connect external wiring to the PROFIBUS adapter as shown below.

1. Connect the PROFIBUS in-going cable to the 12 mm male

connector labeled PBUS IN.

2. Connect the PROFIBUS out-going cable to the 12 mm female

connector labeled PUBS OUT.

3. Connect 24V dc power to sensor voltage for adapter and input

module power.

4. Connect 24V dc power to output voltage for output module

power.

IMPORTANT

Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2 inch
pounds).

Name

Pin
Number

Description

+5VBUS

1

Supply voltage of the
terminating resistance

A-Line

2

Negative RxD/TxD according
to PROFIBUS specification

GNDBUS

3

Supply voltage of the
terminating resistance
(GND)

B-Line

4

Positive RxD/TxD according
to PROFIBUS specification

Shield

5

Connected to Protective
Ground

2

1

1

2

4

3

3

4

5

5

Male
connector
(PBUS IN)

Female
connector
(PBUS OUT)