User Interface

Label

Color

State

Status

Yellow Power On

Indicator

Green Output

Energized Indicator

Red Margin/

SCP Indicator

Light/Dark

Operate Switch

Sensitivity Adjustment

Top View Detail

Output

Green

OFF

Sensor output de-activated

ON

Sensor output activated

Margin/SCP

Red

OFF

Margin < 2.5

ON

Margin >2.5

Flashing

Output SCP active

Power

Yellow

OFF

Sensor not powered

ON

Sensor powered

Dimensions—mm (inches)

63.5

(2.5)

75

(2.9)

Connector Version

13.97 (0.550)

17.78 (0.700)

Micro Style

Mini Style

Typical Response Curves

0.3m

(1i)

51mm

(2I)

O

per

atin

g

M

ar

gi

n

Operating Distance

15m

(50i)

1.5m

(5i)

0.6m

(2i)

3m

(10i)

1

2

4

8

10

20

40

80

100

76mm (3I)

Reflector

32mm (1.25I)

Reflector

16mm (0.625I)

Reflector

Installation

The sensor must be mounted on a firm, stable surface or

support. A mounting platform which is subject to excessive

vibration or shifting may cause intermittent operation. All

wiring between the sensor and the automation system should

conform to the National Electric Code and all applicable local

codes. See wiring diagrams for proper connections.

When power is applied to the sensor, the yellow indicator will

turn ON. Visually sight the sensor at the reflector until the

green indicator turns ON (with sensor in light operate mode)

or OFF (with sensor in dark operate mode). Continue to align

the sensor vertically and horizontally until the red indicator

turns ON.

Once the sensor has been properly aligned, the sensitivity can

now be set. This is accomplished through the use of the

sensitivity knob on the user interface panel. Open the top

cover to access this knob. The default setting is in the full

clockwise position which will provide maximum sensitivity and

range. Turn the knob counterclockwise until the red indicator

turns OFF. This indicates that the threshold where the sensor

is receiving at least 2.5X the required amount of light (margin)

necessary to activate the output. Turn the knob clockwise to a

point where the indicator just turns ON. Normal industrial

environments range from moderately dusty to extremely dirty.

A higher operating margin is typically desirable to overcome

the accumulation of dust/dirt on the optics lens over a period

of time. Refer to the Typical Response Curve to determine the

margin versus distance characteristics of the sensor. Close

the top cover securely.

QD Cordsets and Accessories

Description

Catalog Number

1.8m (6ft) 5-pin, Mini QD Cordset

889N- F5AF- 6F

76mm (3in) Diameter with Center Mount Hole

92- 39

32mm (1.25in) Diameter

92- 47

Publication 75002--296--01(B)

November 2000