Publication 2727-IN003B-MU-P

Installation Instructions

MobileView Download Cable

(Catalog Number 2727-MRC1)

English

The MobileView Download Cable (2727-MRC1) is an accessory for the following
MobileView terminals:

MobileView Machine Terminal MT750

MobileView Guard G750 Machine Terminal

Cable Overview

The 4 meter (13.12 foot) download cable is used with Boot-Loader software to
download software to the MobileView MT750/G750 terminals. It can also be used
with Active-Sync software to transfer data to and from your computer.

Download Cable Pinout Description

1

2

4
5

Tx

Rx

Gnd

3

5

9

MobileView

Serial Port S2 Connector

(female)

MobileView
10-pin Latch

(male connector)

PC

9-pin DSUB

(female connector)

2

10

1

9

1*

7*

2*

6

3

To

To

ActiveSync

ActiveSync

ActiveSync

1

9

Ader 1

4 meter (13.2 foot)

1

PC 9-pin

(male connector)

1

* Pins 1, 2 and 7 are connected together on the CPU board in the MobileView terminal. They are
used for the ActiveSync signal. If you make your own cable, do not elimiate these 3 wires.