Wiring the new circuit – Rockwell Automation 2364F DC Link Fuse Upgrade Kit for RGU Parallel w/ NRU User Manual

Page 8

Advertising
background image

8

DC Link Fuse Upgrade Kit for RGU in Parallel with NRU

Wiring the New Circuit

Important: Use the enclosed stranded 14 gage wire (Belden 30614 or

equivalent). Use the red wire for 115Vac signals and the white
wire for 115Vac neutral. Use the enclosed wire tags.

1. Connect the normally closed Microswitch contacts (contacts that open

when the fuses blow) on the fuses in series with the new relay coil
(CR5). The normally closed contact is between terminal 1 and 2 on each
Mircroswitch.

Figure 7

defines the terminals on the Microswitch.

Figure

8

illustrates the contacts inside the Microswitch. Refer to

Figure 9

for

RGUs with two fuses. Refer to

Figure 10

for RGUs with four fuses.

Figure 7 Microswitch Terminals

Figure 8 Microswitch Contacts