Polled - the master initiates communication by sending its polled I/O
message to the board. The board consumes the message, updates any
outputs and produces a response containing the input data.

Change-of-State - a production occurs when an input changes. A
heartbeat production occurs if no input condition change occurs within the
expected packet rate. This heartbeat production tells the master that the
board is alive and ready to communicate. Consumption occurs when data
changes and the master produces new output data to the board.

Refer to the table below for the word/bit definitions:

Configure the Parameters

The 1799 I/O boards have eight parameters that are configurable through a
DeviceNet software configuration tool like RSNetWorx for DeviceNet. The
DeviceNet configuration tools require an Electronic Data Sheet (EDS) for
the 1799 I/O boards in order to configure the module’s parameters. The
EDS file can be found at the ODVA Web site (http://www.odva.org).

Use the descriptions in the table below to help you configure the
parameters.

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Produced 0

Input 7

Input 6

Input 5

Input 4

Input 3

Input 2

Input 1

Input 0

Produced 1

Reserved

Input 9

Input 8

Consumed 0

Output 7

Output 6

Output 5

Output 4

Output 3

Output 2

Output 1

Output 0

Consumed 1

Reserved

Output 9

Output 8

Parameter

Description

Baud Rate

Controls the board’s data rate.

Auto-Baud

Enables the board to match the network’s data rate. When enabled,
Baud Rate parameter is ignored.

Input Off-to-On
Filter Time

Controls the amount of time the input must be in the ‘on’ state
before the board reports the input as ‘on.’

Input On-to-Off
Filter Time

Controls the amount of time the input must be in the ‘off’ state
before the board reports the input as ‘off.’

Output Idle State

Controls the state of each output when the DeviceNet master is in
an idle state.

Advertising