Troubleshooting with the indicators, Specifications – Rockwell Automation 1798-IB4D FlexArmor 24V dc Diagnostic Sinking Input Module User Manual

Page 6

Advertising
background image

6 FlexArmor 24V dc Diagnostic Sinking Input Module

Publication 1798-IN010A-EN-P - April 2002

Troubleshooting with the Indicators

The following table describes status indicators on the diagnostic input

modules.

Specifications

I/O Status Indicators

Function

Indicator

Status

Inputs

Diagnostic LED

Yellow
Off

Solid Red
Blinking Red
Off

Input ON
Input OFF

Sensor Power Short
Off Wire
Normal

Specifications - 1798-IB4D

Module Type

Digital Input, Sinking

Number of Channels

1 group of 4

Sensor Source Current

50 mA per connector

On-state Voltage

10-28.8V dc; 24V dc nominal

On-state Current

2-12 mA; 8 mA @ 24V dc

Off-state Voltage

5V dc maximum

Off-State Current

1.5 mA minimum

Channel Impedance

4.6K

maximum

Isolation Voltage

850V dc channel-to-system for 1s

Delay Times: Off to On

On to Off

256 us, 512 us, 1 ms, 2ms
4 ms, 8 ms, 16 ms, 32 ms
(Selectable; 256 us default)

FlexBus Current

80 mA maximum

Power Dissipation

2.0W @ 28.8V dc

Thermal Dissipation

6.8 BTU/hr. @ 28.8V dc

Indicators

4 channel status - yellow
4 diagnostic indicators- red

External DC Power

Voltage (24V dc nom.)
Current

10-28.8V dc; 5% AC ripple
300 mA maximum

Dimensions
(H x D x W)

118 mm x 57 mm x 40 mm
4.63 in. x 2.25 in. x 1.58 in.

Operational
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)