Flexarmor 24v dc diagnostic sinking input module 7 – Rockwell Automation 1798-IB4D FlexArmor 24V dc Diagnostic Sinking Input Module User Manual

Page 7

Advertising
background image

FlexArmor 24V dc Diagnostic Sinking Input Module 7

Publication 1798-IN010A-EN-P - April 2002

Specifications - 1798-IB4D (continued)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–40 to 85°C (–40 to 185°F)

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on power ports
±2kV at 5kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Conductors

See publication DN-6.7.2

Enclosure

Meets IP67

Agency Certification
(When product is
marked)

c-UL-us UL Listed Industrial Control Equipment, certified for

US and Canada

UL

UL Listed Industrial Control Equipment

CE

1

European Union 89/336/EEC EMC Directive,

compliant with:

EN 50081-2; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial

Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

1

Australian Radiocommunications Act, compliant

with: AS/NZS 2064; Industrial Emissions

1. See the Product Certification link at www.ab.com for Declarations of Conformity,

Certificates, and other certification details.