Component Definition and Maintenance
Chapter 3
Figure 118 - Terminal locations on 600W AC/DC Power Supply (Cosel)
Output Calibration
Ensure the output of the supply is 56V DC.
There is a potentiometer on the top of the power supply that adjusts the 56 Volt
DC output for the power supply. Isolate the output of the power supplies;
multiple supplies in series will affect your measurements. With the control power
on and the output of the AC/DC Converter isolated from the drive control,
adjust the potentiometer until the output equals 56 volts DC. Perform this test
on each power supply. When all adjustments are complete, reconnect the power
supply to the circuit and re-measure the output. Readjust if necessary.
If it is not possible to maintain 56 V DC, the power supply may be faulty.
Terminal/Connections
Descriptions
(600W Cosel Power Supply)
Single Phase Input
DC Outputs
Control Signals
Air Flow
FRONT VIEW
P1-AC Input
PIN#
LABEL
AC (L)
Live
AC (N)
Neutral
NC
No Connection
FG
Earth
P2-DC Output
PIN#
LABEL
+
+56V
–
+56V COMM
P3-Fail Output
PIN#
LABEL
CN1
1-2 Connected
3-4 Connected
5, 6, 7, 8, 9, 10 N/C
CN2
N/C
CN3
7 - Alarm
8 - Alarm GND