Snubber capacitance (sgct device) – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - ForGe Control User Manual
Page 67

Rockwell Automation Publication 7000-UM202B-EN-P - June 2014
67
Component Definition and Maintenance
Chapter 3
to determine the appropriate snubber resistance value
for the current rating of the SGCT used.
If the resistor is found to be out of tolerance, refer to page
for detailed
instructions on replacing the snubber resistor assembly.
Snubber Capacitance (SGCT Device)
Turn the multimeter from the resistance to capacitance measurement mode.
Verify the snubber capacitor by measuring from the test point to the heat sink
adjacent to the right for standard rectifiers, or from heat sink to heat sink. For
SPS rectifiers, measure from the test point to pin 1 of the Phoenix connector that
plugs into J1 of the SPS board (disconnect the J1 connector from the SPS board
first).
Figure 57 - Snubber Capacitor Test
Heatsink
Heatsink
Snubber
Resistor
Snubber
Capacitor
Sharing Resistor
SGCT
Test Point
Measure capacitance
between heat sink
and test point (or
from heat sink to
heat sink)
Snubber test point