Filter cutoff – Rockwell Automation 1794-OE8H FLEX I/O HART Analog Modules User Manual User Manual
Page 124
Advertising

Publication 1794-UM063A-EN-P - March 2006
E-4 Configure the 1794-IE8H Module in RSLogix 5000 Software Over the ControlNet Network
Filter Cutoff
The generic profile sets all of the filter bits to 0, which is an invalid value. You
must set these bits to a valid value or you will get a diagnostic error value of 2.
Channel
Bits
0…3
[Adapter Name]:[Slot]:C.Data[0].5
[Adapter Name]:[Slot]:C.Data[0].6
[Adapter Name]:[Slot]:C.Data[0].7
4…7
[Adapter Name]:[Slot]:C.Data[1].5
[Adapter Name]:[Slot]:C.Data[1].6
[Adapter Name]:[Slot]:C.Data[1].7
Filter Cutoff Bits
Description
7
6
5
0
0
0
Not Valid
0
0
1
Not Valid
0
1
0
Not Valid
0
1
1
10 Hz (100 ms)
1
0
0
4 Hz (250 ms)
1
0
1
2 Hz (500 ms)
1
1
0
1 Hz (1 s)
1
1
1
0.5 Hz (2 s)