Diagnostic Status
Bits
[Adapter Name]:[Slot]:I.Data[10].0
[Adapter Name]:[Slot]:I.Data[10].1
[Adapter Name]:[Slot]:I.Data[10].2
[Adapter Name]:[Slot]:I.Data[10].3
Diagnostic Description
Bit 3
Bit 2
Bit 1
Bit 0
Normal
0
0
0
0
Calibration Failure
0
0
0
1
Configuration Failure
0
0
1
0
Message Failure
0
0
1
1
Lead Break Detection
0
1
0
0
EEPROM Failure
0
1
0
1
RAM Failure
0
1
1
0
ROM Failure
0
1
1
1
Calculation Failure
1
0
0
0
Data Out of Range
1
0
1
1