Armature SCR Replacement (for 3000A 1395 Drives)
3
Preliminary Steps
Before replacing the armature SCRs, shut off the drive power, 
wait five minutes for the voltage to discharge, open the bridge 
bay door, and remove the Lexan™ shielding.
Removing the Heatpipe Assembly
1.
Using a voltmeter, test the voltage across the three phases, 
then across the heatpipe assembly components (including the 
SCRs).
2.
Unplug the SCR leads from all the armature-pulse trans-
former boards. (For SD3100 drives, tag all the SCR leads 
and disconnect them from the pulse-gate amplifier boards.)
3.
Remove the armature-pulse transformer board panel by 
releasing the black latches on the left and right sides of the 
panel.
4.
Disconnect the three thermal switches and remove the wiring 
from the mounting clips.
5.
Remove the two bolts which connect the assembly to the out-
put busbar.
6.
Remove the two bolts which connect the center heatpipe to 
the incoming AC busbar.
7.
Remove the two bolts from the top of the assembly where the 
Glastic™ shroud is mounted to the back plane.
8.
Lift the assembly out from the drive.
!
ATTENTION: If there is any voltage present, 
remove the source of the voltage and check for 
voltages again before proceeding to the next step.
!
ATTENTION: The heatpipe assembly weighs 
about 75 lbs. Take the proper precautions (adhere 
to your company material handling procedures) 
when removing the assembly to prevent personal 
injury and damage to the equipment.