Rockwell Automation Publication 7000-IN010D-EN-P - January 2014

4

Handling, Inspection, and Storage of Medium Voltage Line Filter Capacitors

Step 1:

Receive the LFCs

Receive the crate into the work site.

Verify the correct parts have been received: You need to match the capacitors
contained in the shipping crate with the VFD into which they will be installed.

Step 2:

Inspect the LFCs

Remove the top cover from the shipping crate, remove the capacitors (see
Figures 1 through 3), and inspect the capacitors for damage – i.e. cracks or chips
in the porcelain bushings, impact or cracks in the LFC case, or leakage of oil.

Figure 1 - LFC Lifting/Mounting Bracket Location

WARNING: Do not handle the LFC by the bushings. The bushings are fragile.
Handle the LFC using the side mounted lifting/mounting brackets as shown in
Figure 1. Due to the weight of the LFC (approximately 150 lbs. / 70 kgs.), use
proper and safe lifting techniques, preferably with a lifting device or manually
with more than one person.

Lifting Bracket

Lifting Bracket