Rockwell Automation 2090-DA-BAT2 Low-profile Connector Kit for I/O and Feedback Installation Instructions User Manual

Installation instructions, Install the low-profile connector kit

Advertising
background image

Installation Instructions

Low-profile Connector Kit for I/O and
Feedback Signals

Catalog Numbers 2090-K2CK-COMBO, 2090-DA-BAT2

Install the Low-profile Connector Kit

2090-K2CK-COMBO Connector Kit Specifications

Attribute Value

Current rating

1.0 A max

Screw terminal wire size

Single
Dual

0.06…1.31 mm

2

(30…16 AWG)

0.14…0.20 mm

2

(26…24 AWG)

(1)

(1)

Two conductors can connect to a single terminal providing the conductors are the same cross section and the construction of both is stranded.
Terminals 22 and 27 (24VCOM_REG and 24V_REG), 28 and 38 (24VCOM and 24VPWR), and 39 and 44 (24VCOM and 24VPWR) can require
connection of dual conductors.

Recommended wire strip length

5 mm (0.2 in.) single conductor

ATTENTION: This connector kit contains electrostatic discharge (ESD) sensitive parts that can be
damaged if you do not follow ESD control procedures. If you are unfamiliar with ESD control
procedures, refer to Guarding Against Electrostatic Damage, publication

8000-4.5.2

, or any other

applicable ESD protection handbook.

If necessary, turn clamp
over to hold small wires

secure.

Secure braided
shield under clamp.
Make sure shield
contacts ground pad.

Tie wrap secures wire bundles.

Shrink-wrapped Insulation

Follow these steps to form a compact connection.
1. Push the insulation down-and-over itself.
2. Move the insulation so it butts against the

outside wall of the cover.

3. Tape or shrink-wrap the end of the insulation

to the cable.