Mounting the cutout adapter and new terminal, Disconnect the terminal, Remove the existing terminal – Rockwell Automation 2711P-RAT12E Adapter Kit for PanelView 1400eTouch Screen Terminal Cutout User Manual

Page 3: Attach the cutout adapter plate to the panel

Advertising
background image

Publication 2711-IN023B-EN-P - November 2002

Adapter Kit for PanelView 1400e Touch Screen Terminal Cutout 3

Mounting the Cutout
Adapter and New Terminal

Follow the steps below to mount the new terminal into the existing
PanelView 1400e Touch Screen terminal cutout.

Disconnect the Terminal

1. Disconnect power at the source and remove the power cord

from the PanelView 1400e terminal.

2. Disconnect all communication cables from the PanelView 1400e

terminal.

Remove the Existing Terminal

1. Remove the mounting clips or nuts and washers that secure the

PanelView 1400e terminal to the panel.

2. Slide the existing terminal out from the terminal.

Attach the Cutout Adapter Plate to the Panel

1. Align the cutout adapter to the desired position.

2. Push the cutout adapter plate onto the panel until the gasket

material is flush with the front of the panel.

3. Using the 12 nuts with flat washers, fasten the cutout adapter

plate to the panel.

Tighten the washers until the gasket is slightly compressed.

4. Using the torque wrench, tighten the nuts to no more than 10

inch-pounds (a torque of 10 inch-pounds attains a NEMA Type
4X rating). Do not over-tighten.

ATTENTION

Make sure that the power cord of the PanelView 1400e terminal is
disconnected, and that all cables have been disconnected from the
rear of the terminal.