PanelView 550 Terminals 15
Publication 2711-IN009E-EN-P - February 2009
EtherNet/IP Protocol
The PanelView terminal is initially set to DHCP with BootP support (Dynamic Host 
Configuration Protocol) enabled. If your network has a DHCP/BootP server, you 
can connect the PanelView terminal to the EtherNet/IP network and the 
DHCP/BootP server will automatically establish an IP address. If your network does 
not have a DHCP/BootP server, you need to program an IP address. This is done by 
accessing Configuration Mode on the PanelView terminal and selecting 
Communication Setup. For details, refer to the PanelView Standard Operator 
Terminals Manual, publication 
.
ControlNet Protocol
Battery Removal and Disposal
The terminal contains a lithium battery, which is intended to be replaced during the 
life of the product.
IMPORTANT
If a PanelView is connected to an EtherNet/IP network and has the same IP address as 
another device on the network, both devices will drop off the network.
IMPORTANT
When making ControlNet connections, only use the PanelView Channel B for redundant 
communications. Connecting Channel B to a Channel A only ControlNet network will 
result in:
•
the PanelView not being able to communicate over the network.
•
a PanelView communications fault after several minutes.
ATTENTION
The clock module contains lithium. Do not dispose of the battery in a fire or incinerator, or 
the clock module may explode. Follow disposal regulations in your area for lithium 
battery disposal.
At the end of its life, the battery contained in this product should be collected separately 
from any unsorted municipal waste.