RGU™ DC Suppressor Replacement

3

Publication 2364F-5.11 - November 1998

Preliminary Steps

Before replacing the DC suppressor, shut off the power; wait five
minutes for the voltage to discharge; and open the bay door.

Removing the DC Suppressor

1. Using a meter, test the voltage across the DC bus terminals on the

power structure, then across the DC suppressor terminals.

2. Remove the four screws from the Lexan™ shield on the DC sup-

pressor.

Note: If unable to remove the shield, take the four mounting bolts
out, set the assembly on a stable surface, and remove the shield.

3. Disconnect the bus leads and the PE ground lead.

4. Remove the four mounting bolts and remove the suppressor.

!

ATTENTION: If there is any voltage present,
remove the source of the voltage and check for
voltages again before proceeding to the next step.

D C B us Lead (-)

PE Lead

DC Bu s Lead (+ )

4

2

3

2

4

3