Rockwell Automation 1798-DFTP2 FlexArmor DeviceNet Field Termination Plug User Manual
Page 4
                                    Advertising
                                    
                                        
                                    
                                
                                 
4 FlexArmor DeviceNet Field Termination Plug
Publication 1798-IN004A-EN-P - January 2001
2. Insert connector into mating connector on the DeviceNet FTP
module.
3. Connect 24V dc power to sensor voltage for adapter and input
module power.
Connect 24V dc power to output voltage for output module 
power.
WHT Wire
4
CAN High
RED Wire
2
+V
*CAN=Controller Area Network
Connect
Connector Pin
To
42538
M12 Male connector (In)
1
2
3
4
5
1
2
3
4
5
M12 Female connector 
(Daisy Chain Out)
1
2
3
4
5
1
2
3
4
5
M18 Male 
connector (In)
M18 Female 
connector 
(Daisy Chain Out)
42653
DFTP1
DFTP2
2
1
3
4
Pin
Function
1
Output Power +
2
Sensor Power +
3
Sensor Power -
4
Output Power -