Troubleshooting with the indicators, Devicenet field termination plug specifications – Rockwell Automation 1798-DFTP2 FlexArmor DeviceNet Field Termination Plug User Manual

Page 5

Advertising
background image

FlexArmor DeviceNet Field Termination Plug 5

Publication 1798-IN004A-EN-P - January 2001

Troubleshooting with the Indicators

The table describes status indicators on the Field Termination Plug.

DeviceNet Field Termination Plug Specifications

Following are specifications for the DeviceNet Field Termination Plug

Indicator

Status

Green
Off

Power ON
Power OFF or reverse polarity

Voltage Rating

28.8V dc maximum

Sensor and Adapter Current

2.5A maximum

Output Current

10A maximum

Sensor/Output Voltage

10-28.8V dc

Sensor/Output Power Connector

0.875 in male

Dimensions (H x D x W)

121 mm x 36.3 mm x 42 mm
4.75 in. x 1.43 in. x 1.65 in.

Environmental Conditions
Operational Temperature
Storage Temperature
Shock Operating
Non-operating
Vibration

-20 to 60°C (-4 to 140°F)
-40 to 85

°

C (-40 to 185

°

F)

30g peak acceleration, 11(±1) ms pulse width
50g peak acceleration, 11(±1) ms pulse width
Tested 5g @ 10-500 Hz per IEC 68-2-6

Conductors

See publication DN-6.7.2

Enclosure

Meets IP67

Agency Certification
(When product is marked)

CUL listed
UL Hazardous Class 1, Division 2, Groups A, B, C, D
certified
CE marked for all applicable directives

marked for all applicable acts

N223