sales representative.
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1kHz sine wave 80% AM from 150 kHz to 80 MHz
Emissions
CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating
None (open-style)
Power Conductors
Wire Size
Category
12 gauge (4 mm
2
) maximum solid or stranded copper wire rated at
75 °C or greater
3/64 in. (1.2 mm) insulation max.
1
(1)
Certifications
(when product is marked)
C-UL-US UL Listed Industrial Control Equipment for U.S. and Canada
C-UL-US UL Listed for Class I, Division 2 Groups A, B, C and D for
U.S. and Canada
CE
(2)
European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4, Industrial Emissions
EN 61326, Meas./Control/Lab., Industrial Requirements
EN 61000-6-2, Industrial Immunity
CE
(2)
European Union 73/23/EEC LVD Directive, compliant with:
EN 61131-2, Programmable Controllers
C-Tick
(2)
Australian Radiocommunications Act, compliant with:
AS/NZS 2064, Industrial Emissions
(1)
Use this conductor capacity information for planning conductor routing. Refer to publication 1770-4.1, Industrial