1.

The PowerFlex 7000 Software Updater

uses the following Ethernet ports:

TCP 20,21 for FTP transfer of files

UDP 20034 for the discovery process of drives

UDP 514 for status strings for each step of the update process

To function properly, any firewall that may be utilized must not block these ports, or the firewall temporarily
disabled.

2.

If the PC has multiple Ethernet ports (referred to as MultiHoming) and problems are encountered, disable all ports
except the one connected to the drive network.

3.

If a Comm Error is encountered while using the PowerFlex 7000 Software Updater

during the download operation,

press the Reset button on the HMI Interface Board and try the download process again.