Trusted, Module t8424, Rack 5: line_flt – Rockwell Automation T8424 Trusted TMR 120Vac Digital Input Module User Manual

Page 17: Rack 6: discrep

Advertising
background image

Trusted

TM

Module T8424

Issue 8 Sep 11

PD-T8424

17

3.2.5. Rack 5: LINE_FLT

Channel

Description

1

Field input channel 1 line fault

2

Field input channel 2 line fault

40

Field input channel 40 line fault

Table 8 Rack 5: Line Fault descriptions

The line fault input is reported as true (logic ‘1’) for a line fault condition (for this module, only FTA to
module Open Circuit). The logic state is the majority voted value.

When the TMR Processor detects a 2oo3 channel fault or discrepancy, or if the input module is
simulated, the line fault input is set to True.

3.2.6. Rack 6: DISCREP

Channel

Description

1

Discrepancy status inputs 1 to 16 (input 1 is LSB, bit 0)

2

Discrepancy status inputs 17 to 32 (input 17 is LSB, bit 0)

3

Discrepancy status inputs 33 to 40 (input 33 is LSB, bit 0)

Table 9 Rack 6: DISCREP bit descriptions

Each of the integers reports the discrepancy status of 16 input channels. The corresponding bit within
the integer is set to ‘1’ when a discrepancy condition is detected on that input channel’s input state
(rack 2). For example, if slice B of the input module reports the state of channel 4 as state 5, while
slices A and C report channel 4 as state 2, then Slice B has a channel discrepancy for channel 4. In
this case, bit 3 of channel 1 on the Discrepancy board would be set to ‘1’.

Advertising