Field termination unit (ftu), Trusted, Module t8424 – Rockwell Automation T8424 Trusted TMR 120Vac Digital Input Module User Manual

Page 7

Advertising
background image

Trusted

TM

Module T8424

Issue 8 Sep 11

PD-T8424

7

Figure 2 shows a simplified functional block diagram of the Trusted

TM

TMR 120VAC Digital Input

Module.

Figure 2 Functional Block Diagram

1.1. Field Termination Unit (FTU)

The Field Termination Unit (FTU) is the section of the I/O module that connects all three FIUs to a
single field interface. When installed in a Trusted

TM

Controller or Expander Chassis, the FTU field

connector interconnects to the I/O cable assembly attached at the rear of the chassis.

The SmartSlot link is passed from the HIU to the field connections via the FTU. These signals go
directly to the field connector and maintain isolation from the I/O signals on the FTU. The SmartSlot
link is the intelligent connection between active and standby modules for co-ordination during module
replacement.

FTA

Input
Field

Device

F

ie

ld

T

e

rm

in

a

ti

o

n

U

n

it

(F

T

U

)

SLICE A

IMB A

FRONT PANEL

A/D

CONVERTER

FIELD LOGIC

CONTROL

IS

O

L

A

T

IO

N

B

A

R

R

IE

R

SLICE POWER

SUPPLY

HOUSEKEEPING

FIU

SLICE CONTROL A

TIME STAMP

BUS INTERFACE

HOUSEKEEPING

MODULE TEMP

SUPPLY DIAG

DSP REFERENCE

REDUNDANT

SUPPLY

24V1

24V2

HIU POWER

FIU POWER

FRONT PANEL
VOTING LOGIC

SLICE B
SLICE C

SERIAL DISPLAY LATCHES

VOTED STATUS DISPLAY LEDs

HEALTH

INDICATORS

SLICE B

SLICE C

IMB B

IMB C

HIU

VAC