Trusted

TM

Module T8431

Issue 16 Sep 11

PD-T8431

15

3. Application

3.1. Module Configuration

There is no configuration required to the physical input module. All configurable characteristics of the
module are performed using tools on the EWS and become part of the application or system.ini file
that is loaded into the TMR Processor. The TMR Processor automatically configures the input module
after applications are downloaded and during Active/Standby changeover.

The IEC1131 TOOLSET provides the main interface to configure the input module. Details of the
configuration tools and configuration sequence are provided in PD-8082B Trusted

TM

Toolset Suite.

There are three procedures necessary to configure the input module. These are:

1. Define the necessary I/O variables for the field input data and module status data using the

Dictionary Editor of the IEC1131 TOOLSET.

2. Create an I/O module definition in the I/O Connection Editor for each I/O module. The I/O

module definition defines physical information, e.g. Chassis and Slot location, and allows
variables to be connected to the I/O channels of the module.

3. Using the Trusted

TM

System Configuration Manager, define custom LED indicator modes,

per-channel threshold levels and noise filtering, and other module settings.

3.2. T8431 Complex Equipment Definition

The T8431 I/O Complex Equipment Definition includes 8 I/O boards, referenced numerically by Rack
number:

Rack

I/O Board

Description

Data Type

Direction No. of

Channels

1

THRSHIN

OEM Parameters

-

-

-

Field Input Status

Integer

In

9

2

STATE

Field Input State

Integer

In

40

3

AI

Field Input Engineering Unit

Integer

In

40

4

THRSHOUT

Threshold data

Integer

Out

11

5

LINE_FLT

Line Fault Status

Boolean

In

40

6

DISCREP

Channel Discrepancy

Integer

In

3

7

HKEEPING

Housekeeping Registers

Integer

In

51

8

INFO

I/O Module Information

Integer

In

11

Table 3 Complex Equipment Definition

There are two OEM parameters included in the first rack (THRSHIN Board). These OEM parameters
define the primary module position; declaring the module’s chassis and slot location. There is no need
to define the secondary module position within the IEC1131 TOOLSET. Where systems may be
required to start-up with a module in the secondary position as the active module, e.g. primary module
is not installed when application is started, the secondary module’s position should be declared in the
module definition of the System Configuration Manager.