Trusted, Module t8431, Rack 1: thrshin – Rockwell Automation T8431 Trusted TMR 24Vdc Analogue Input Module - 40 Channel User Manual

Page 16

Advertising
background image

Trusted

TM

Module T8431

Issue 16 Sep 11

PD-T8431

16

OEM Parameter

Description

Notes

TICS_CHASSIS

The number of the
TrustedTM Chassis
where the primary I/O
module is installed

The TrustedTM Controller Chassis is 1, and
TrustedTM Expander Chassis are 2 to 15

TICS_SLOT

The slot number in the
chassis where the
primary I/O module is
installed

The I/O module slots in the TrustedTM
Controller chassis are numbered from 1 to 8.
The I/O Module slots in the TrustedTM Expander
Chassis are numbered from 1 to 12

Table 4 OEM Parameters

3.2.1. Rack 1: THRSHIN

This board allows the current thresholds for an analogue input channel to be read by the application,
under control of the THRSHOUT board (see section 3.2.4).

Channel

Description

1

Channel number being read. Range 0 to
41.

2

States 2 > 1 falling threshold

3

States 1 > 2 rising threshold

4

States 3 > 2 falling threshold

5

States 2 > 3 rising threshold

6

States 4 > 3 falling threshold

7

States 3 > 4 rising threshold

8

States 5 > 4 falling threshold

9

States 4 > 5 rising threshold

Table 5 Rack 1: Threshold input descriptions

THRSHIN reads in the module threshold values controlled by THRSHOUT in Rack 4. See Table 1 for a
graphical representation of the states and thresholds.

Advertising