Rockwell Automation SP600 Quick Start 20-150HP User Manual

Quick start, Quick start instructions instructions, Wiring power up parameter setting

Advertising
background image

Quick Start

Quick Start

Instructions

Instructions

Wiring

Power Up

Parameter Setting

Reliance Electric Drives
SP600 AC Variable Frequency
Inverter - 20 HP to 150 HP
6SB Series Model Numbers

Quick Start Instructions:
A quick reference to some basic
configurations and drive features.

OIM Keypad

The SP600 keypad allows for drive setup,
parameter adjustment, monitoring and
drive diagnostics.

Operator Interface Module (OIM)

Start-Up

Parameters

Control Src

Sel

Diagnostics

Display

Memory
Storage

Device

Select

User

Display

By Groups

Changed Params

P Numbers

Speed Ref A Sel

Logic Source Sel

Password

Load Frm Usr Set

Save to User Set

Reset Defaults

Active User Set

Language

Function Keys

Reset Display

Display Video

Display Timeout

Monitor

Device Identity

Fast PwrUp Mode
Contrast

Set Wrt Prot PW

Set Acc Lvl PW

Set Access Lvl

QuickStart

Motor Data

Configure I/O

Ref Setup

Speed Limits

Input Voltage

Motor Tests

Done

ESC/
PROG

Press

Press

Press

to move between menu items

to select a menu item

to move 1 level back in the menu structure

ESC/
PROG

Logout

Menu options
dependent upon
devices connected.

Press

to move between icons

OIM Version

Device Version

View Fault Queue

Device Items

Status Info

Fault Info

Tech Support

Optional
Remote Keypad
RE4LCD-PNL
To use as control
source, set P89
and P90 = DPI
Port 2

NOTE: This material is not intended to
provide operational instructions.
Appropriate Reliance Electric Drives
instruction manuals precautions should be
studied prior to installation, operation, or
maintenance of equipment.

Quick Start

OIM Quick Start Menu

The Quick Start Parameters can be
accessed via the keypad menu icon. Once
into the selection list the following
parameters can be set to configure the
drive to the installed motor.

1) QuickStart

••

Stop Mode A (Ramp)

••

Motor NP FLA (Drive Dependant)

••

Minimum Speed (0.0 Hz.)

••

Maximum Speed (60.0 Hz.)

••

Accel. Time 1 (10.0 sec.)

••

Decel. Time 1 (10.0 sec.)

••

Speed Reference A select (OIM)

••

Digital IN2 Select (Start)

(Defaults)
The default configuration is defined as:
Drive Voltage rating = Motor Voltage
Start/Stop control = OIM
Speed Reference = OIM
Control Mode = Sensorless Vector

If the drive default configuration is to be
used for initial startup then the above
parameters are the only settings required.

If the user needs to customize the drive
configuration different than the default
setting, then the user should verify the
parameter settings accessible throughout
the start-up menu.

2) Input Voltages

••

400/480 VAC

3) Motor Nameplate Data

••

Motor Power Units

••

Motor Power

Quick Start (cont.)

3) Motor Nameplate Data con’t

••

Motor FLA

••

Motor Volts

••

Motor Hertz

••

Motor RPM

4) Motor Tests

••

Direction

••

AutoTune

5) Speed Limits

••

Minimum, Maximum

••

Direction Limit

••

Stop Mode

6) Reference Setup

••

OIM Keypad, Terminal Block,
Network, Other

7) Configure I/O

••

Digital Inputs/Outputs

••

Analog Outputs

Control Mode

(P53) Torque Perf Mode
Control performance can be selected
from:

••

Sensorless Vector (default)
Highest performance mode of control

••

SV Economize
Sensorless Vector with energy saving

••

Custom V/Hz
Basic open loop control. Multi-motor
application

••

Fan/Pump: V/Hz
Provides for a Fan load V/Hz curve

START-UP

ATTENTION: Rotation of the motor in an
undesired direction can occur during this
procedure Autotune (61) = Rotate Tune
(2). To guard against possible injury and/or

equipment damage, it is recommended that the motor be
disconnected from the load before proceeding.

!