Power Wiring

Input Voltage: Determined by model
number. Voltage Class configures the drive
for International voltage supplies.

Control Wiring

Default:

(Out-of-the-box) configuration is

for Keypad control. The user will be able
to start the controller from the drive
mounted operator interface module (OIM).
Speed adjustment using UP/DOWN keys
while in Monitor Display mode.

Stop Start

L1

R

L2

S

L3

T

+DC BRK T1

U

T2

V

T3

W

PE

PE

M

BR1 BR2

ATTENTION: The SP600 does not
provide branch circuit protection.
The user must install the proper
protection devices.

!

24

25

26

28

Supply

Com.

Logic

Com.

+24

VDC

Terminal Assignments

Term.#

Signal Name

Default

1

Analog Volts In1 (-)

2

Analog Volts In1 (+)

Not Assigned

3

Analog Volts In2 (-)

Default 0-10 VDC

4

Analog Volts In2

(+)

5

Reference Common

6

Analog Volts Out1

(-)

Output Frequency

7

Analog Volts Out1

(+)

See Param. 342

8

Analog Current Out1(-)

Not Assigned

9

Analog Current Out1(+)

10

Reserved

11

Digital Out1 - NC

Fault*

12

Digital Out1 - C

13

Digital Out1 - NO

14

Digital Out2 - NC

Running*

15

Digital Out2 - C

16

Digital Out2 - NO

17

Analog Current In1

(-)

Default 4-20 mA

18

Analog Current In1

(+)

19

Analog Current In2

(-)

Not Assigned

20

Analog Current In2

(+)

21

-10 VDC Ref. Out

Speed Potentiometer

22

+10 VDC Ref. Out

23

Reserved

24

+24 VDC Output

24 V logic supply

25

Logic Input Common Logic Common

26

24 V Int. Common

Logic Common

27

Digital In 1

Stop/Clear Fault

28

Digital In 2

Start

29

Digital In 3

Function Loss

30

Digital In 4

Jog

31

Digital In 5

Manual

32

Digital In 6

Speed Select 1

D-2991

Reference Wiring

Analog Reference Wiring
(0 to 10 VDC Input)

(P90) Speed Ref A Sel = Analog In1
(P91) Speed Ref Hi = 60 Hz.
(P92) Speed Ref Lo = 0 Hz.
(P320) Analog In Config =..xx00
(P322) Analog In 1 Hi = 10.0 V
(P323) Analog In 1 L0 = 0.0 V
Analog Inputs can be configured for 4-20
mA. See instruction manual.

Analog Output Wiring
(0 to 10 VDC Input)

(P341) Analog Out Absolute = 1
(P342) Analog Out1 Sel = Output Freq.
(P343) Analog Out1 Hi = 10.0 V
(P344) Analog Out1 Lo = 0.0 V

1 2 5 22

Analog In 1 (-)

Common

Analog In 1 (+)

+10 VDC

3

4

5

6

7

8

-

+

CommonA Out

Volts

0-10 VDC

Control Wiring

Two Wire Start/Stop Control

(P89) Logic Source Sel = Terminal Block
(P361) Digital In1 Sel = Not Used
(P362) Digital In2 Sel = Run
(P363) Digital In3 Sel = Function Loss

Three Wire Start/Stop Control

(P89) Logic Source Sel = Terminal Block
(P361) Digital In1 Sel = Stop
(P362) Digital In2 Sel = Start
(P363) Digital In3 Sel = Function Loss

See Parameters P361 to P366 for
configuration of all logic inputs.

24 25 26 27 28 29

Run

Function Loss

Supply Com.

Logic Com.

+24 VDC

24 25 26 27 28 29

Run

Function Loss

Supply Com.

Logic Com.

+24 VDC

Stop

* Form C Relay contact outputs:
NO (Normally Open)
NC (Normally Closed)
C (Common)