Par

Parameter Name

Factory Default

Programmed Value

Par

Parameter Name

Factory Default

Programmed Value

101

Preset Speed 1

5.0 Hz

195

MOP Rate

1.0 Hz/s

102

Preset Speed 2

10.0 Hz

196

Param Access Lvl

Basic

103

Preset Speed 3

20.0 Hz

197

Reset To Defalts

Ready

104

Preset Speed 4

30.0 Hz

198

Load Frm Usr Set

Ready

105

Preset Speed 5

40.0 Hz

199

Save To User Set

Ready

106

Preset Speed 6

50.0 Hz

200

Reset Meters

Ready

107

Preset Speed 7

60.0 Hz

201

Language

Not Selected

117

Trim In Select

Analog In 2

202

Voltage Class

Based on Drive Cat. No.

118

Trim Out Select

xxxxxxxxxxxxxx00

203

Drive Checksum

Read Only

119

Trim Hi

60.0 Hz

209

Drive Status 1

Read Only

120

Trim Lo

0.0 Hz

210

Drive Status 2

Read Only

121

Slip RPM @ FLA

Based on

[Motor NP RPM]

211

Drive Alarm 1

Read Only

122

Slip Comp Gain

40.0

212

Drive Alarm 2

Read Only

123

Slip RPM Meter

Read Only

213

Speed Ref Source

Read Only

124

PI Configuration

xxxxxxxxxx000000

214

Start Inhibits

Read Only

125

PI Control

xxxxxxxxxxxxx000

215

Last Stop Source

Read Only

126

PI Reference Sel

PI Setpoint

216

Dig In Status

Read Only

127

PI Setpoint

50.00%

217

Dig Out Status

Read Only

128

PI Feedback Sel

Analog In 2

218

Drive Temp

Read Only

129

PI Integral Time

2.00 Secs

219

Drive OL Count

Read Only

130

PI Prop Gain

1.00

220

Motor OL Count

Read Only

131

PI Lower Limit

-[Maximum Freq]

224

Fault Frequency

Read Only

132

PI Upper Limit

+[Maximum Freq]

225

Fault Amps

Read Only

133

PI Preload

0.0 Hz

226

Fault Bus Volts

Read Only

134

PI Status

Read Only

227

Status 1 @ Fault

Read Only

135

PI Ref Meter

Read Only

228

Status 2 @ Fault

Read Only

136

PI Fdback Meter

Read Only

229

Alarm 1 @ Fault

Read Only

137

PI Error Meter

Read Only

230

Alarm 2 @ Fault

Read Only

138

PI Output Meter

Read Only

234

Testpoint 1 Sel

499

140

Accel Time 1

10.0 Secs

235

Testpoint 1 Data

Read Only

141

Accel Time 2

10.0 Secs

236

Testpoint 2 Sel

499

142

Decel Time 1

10.0 Secs

237

Testpoint 2 Data

Read Only

143

Decel Time 2

10.0 Secs

238

Fault Config 1

xxxxxxxxx1001x10

146

S-Curve %

0%

240

Fault Clear

Ready

147

Current Lmt Sel

Cur Lim Val

241

Fault Clear Mode

Enabled

148

Current Lmt Val

[Rated Amps] x 1.5

242

Power Up Marker

Read Only

149

Current Lmt Gain

250

243

Fault 1 Code

Read Only

150

Drive OL Mode

Both-PWM 1st

244

Fault 1 Time

Read Only

151

PWM Frequency

4 kHz

245

Fault 2 Code

Read Only

155

Stop Mode A

Ramp

246

Fault 2 Time

Read Only

156

Stop Mode B

Coast

247

Fault 3 Code

Read Only

157

DC Brk Lvl Sel

DC Brake Lvl

248

Fault 3 Time

Read Only

158

DC Brake Level

[Rated Amps]

249

Fault 4 Code

Read Only

159

DC Brake Time

0.0 sec

250

Fault 4 Time

Read Only

160

Bus Reg Ki

450

259

Alarm Config 1

xxxxxx111x111111

161

Bus Reg Mode A

Adjust Freq

270

DPI Baud Rate

125 kbps

162

Bus Reg Mode B

Both-Frq 1st

271

Drive Logic Rslt

Read Only

163

DB Resistor Type

Internal Res

272

Drive Ref Rslt

Read Only

168

Start At PowerUp

Disabled

273

Drive Ramp Rslt

Read Only

169

Flying Start En

Disabled

276

Logic Mask

xxxxxxxxxx1x1111

170

Flying StartGain

4000

277

Start Mask

xxxxxxxxxx1x1111

174

Auto Rstrt Tries

0

278

Jog Mask

xxxxxxxxxx1x1111

175

Auto Rstrt Delay

1.0 Secs

279

Direction Mask

xxxxxxxxxx1x1111

184

Power Loss Mode

Coast

280

Reference Mask

xxxxxxxxxx1x1111

185

Power Loss Time

0.5 Secs

281

Accel Mask

xxxxxxxxxx1x1111

190

Direction Mode

Unipolar

282

Decel Mask

xxxxxxxxxx1x1111

192

Save HIM Ref

xxxxxxxxxxxxxxx1

283

Fault Clr Mask

xxxxxxxxxx1x1111

193

Man Ref Preload

Disabled

284

MOP Mask

xxxxxxxxxx1x1111

194

Save MOP Ref

xxxxxxxxxxxxxx00

285

Local Mask

xxxxxxxxxx1x1111