Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual
Page 15

XM ControlNet Adapter 15
Publication
ICM-IN001A-EN-P - March 2009
CH A and CH B
Viewed
Together
Both Off
Reset, no power or entire network interface
deactivated
Alternating Red/Green
Self test mode
Alternating Red/Off
Bad/invalid node configuration (such as
duplicate MAC ID)
Both Red
Failed link interface or failed module
CH A and CH B
Viewed
Individually
Off
Channel disabled or channel not supported
Flashing Red/Green
Invalid link configuration
Flashing Red/Off
Severe Link error - link fault or no MAC
frames received
Flashing Green/Off
Temporary channel error or listen-only
Solid Green
Normal operation - MAC frames are being
received without detected errors
Back Plane
Status
Off
Device not powered - check module status
indicator
Flashing Red
Recoverable fault has occurred.
One or more connections have timed out.
Applies to ControlNet and XM Bus
connections.
Solid Red
Unrecoverable fault has occurred:
• adapter is “bus off”
• adapter has failed its duplicate MAC
ID check
Flashing Green
Adapter on-line with no connections
established
Solid Green
Adapter on-line with connections
established (normal operation, in run mode)
Indicator
State
Description