Rockwell Automation 36С47 DC Drive Output Contactor Kit 300-500HP User Manual

Page 2

Advertising
background image

1. Disconnect all power to the AĆC VLS Drive before

installing this kit.

DANGER

EQUIPMENT IS AT LINE VOLTAGE WHEN

THE INPUT DISCONNECT IS ON. THE INPUT

DISCONNECT MUST BE OFF BEFORE IT IS

SAFE TO TOUCH ANY INTERNAL PARTS OF

THIS EQUIPMENT. AFTER POWER IS

REMOVED, THE COMMUTATION CAPACIĆ

TORS CAN REMAIN CHARGED. ALLOW

TWO MINUTES BEFORE TOUCHING ANY

INTERNAL PARTS OF THE CONTROLLER.

FAILURE TO OBSERVE THESE PRECAUĆ

TIONS COULD RESULT IN FATAL INJURY.

NOTE: If the Output Contactor Kit and the Control Circuit

Transformer Kit are to be installed, mount the Output

Contactor Kit first because the Control Circuit Transformer

Kit normally occupies the same location as the Output

Contactor Kit. The Control Circuit Transformer Kit must be

relocated as defined in Instruction Sheet D2Ć3014.

2. Disconnect motor leads T1, T2 and T3 from the output

bus bar assembly (Figure 1). Disconnect bus bars

601, 602 and 603 from the output bus bar assembly

(Figure 1). Remove the output bus bar assembly by

removing the four taptite screws. This assembly will

not be used while the Output Contactor Kit is installed.

3. Snap the Auxiliary Contact (76624ĆX) into the cavity on

the front left of the Contactor (Figure 2). Secure with

the captive lock screw provided.

4. Using the four furnished 5/16Ć18 x 1/2" hex washer

head screws, mount the Contactor (705310Ć9R) in the

controller as shown in Figure 2. The mounting holes

are preĆdrilled in the back panel.

5. Using the six furnished 1/4Ć20 x 3/4" hex head cap

screws and six 1/4" flat washers and 1/4" lock

washers, install the three identical Connectors

(610290Ć57A) to the line side of the Contactor. See

Figure 2.

6. Using the three furnished 1/2Ć13 x 1 1/4" hex head cap

screws and the three 1/2" flat washers and 1/2" lock

washers, attach the Connectors to the 601, 602 and

603 bus bars.

7. Using four of the furnished 10Ć32 x 1/2" taptite screws,

mount the Control Transformer (417155ĆS) to the left

of the motor overload relay block as shown in Figure 2.

The mounting holes are preĆdrilled in the back panel.

(It might be helpful to preĆthread the screws in the

mounting holes.)

8. connect the metal jumper supplied with the

transformer between the two center terminals (H

3

and

H

2

) on the input side of the transformer. See Figure 2.

Figure 1. Removing output bus bar assembly.

Figure 2. Controller right bay components.

FUSE IN FUSE BLOCK

METAL

JUMPER

MOTOR OVERLOAD

RELAY BLOCK

CONNECTOR (3)

CONTACTOR

AUXILIARY

CONTACT

CONTROL

TRANSFORMER

OUTPUT BUS BAR

ASSEMBLY

SIDE VIEW

FRONT VIEW

TAPTITE

SCREW (4)

DISCONNECT MOTOR

LEADS T1, T2, T3

BUS BARS

601, 602, 603