Rockwell Automation 36С47 DC Drive Output Contactor Kit 300-500HP User Manual

Page 4

Advertising
background image

connect the other end to the hole preĆdrilled in the

back panel below the Control Transformer. See

Figures 2, 5 and 7.

16. Connect Wire Assembly 608809Ć12RX (labeled 288)

between the Fuse and the Control Transformer. See

figures 2, 5 and 7.

17. Connect Wire Assembly 608809Ć12SC between

terminals 1 and 3 on the Contactor terminal board.

See Figure 5.

18. Referring to Figures 6 and 7 and Table 2, connect Wire

Harness 801553Ć34R beginning in the left bay of the

controller. Route the harness thru the back channel

located above the power module, thru the bottom

opening at the top of the side wall, thru the back

vertical channel to the respective connection points.

Note that leads 11 and 289 will route thru the back

channel located above the Control Transformer.

Harness Lead

Numbers

(both ends)

From

To

388

ă11

381

383

289

Fuse

Relay

Control Transformer H

1

Control Transformer H

4

Control Transformer X

2

Relay

L1 on Contactor

Transformer Line Fuse

Transformer Line Fuse

L2 on Contactor

19. Referring to Figures 6 and 7, connect Wire Harness

801553Ć35R to the Auxiliary Contact installed in Step

3. Route the harness in the front channel (outermost)

located above the Control Transformer, up the front

vertical channel, thru the top opening at the top of the

side wall, thru the front channel located above the

power module, down the front vertical channel, thru

the horizontal channel located above the regulator, to

terminals 43 and 53 on TB1 of the regulator.

20. Support the wire harnesses and assemblies as

necessary with the furnished tyĆraps.

Figure 5. Connecting Wire Assemblies 608809Ć12X, Ć12RX and Ć12SC.

WIRE ASSEMBLY

608809Ć12RX

WIRE ASSEMBLY

608809Ć12SC

CONTACTOR

CONTROL

TRANSFORMER

FUSE

WIRE ASSEMBLY

608809Ć12X

Advertising