Rockwell Automation SB3000 High Pwr SB3000 AC Pwr Modules (RCS) User Manual

Page 58

Advertising
background image

A-2

SB3000 Power Modules (RCS)

Maximum AC Line Variation: +/- 10%

AC Line Frequency: 25, 50, and 60 Hz, +/- 2 Hz

Frequency Rate of Change: 1Hz/sec

Maximum AC Line Current: 534A, 972A, 1457A

Maximum Phase Imbalance: 5%

AC Control Power

AC Input Voltage: 115 VAC

AC Input Frequency: 50/60 Hz

DC Output Power

Minimum Output Voltage: 1.414 x VAC x 1.1 x 1.1

Maximum Output Voltage: 900V

Output Voltage Regulation: +/- 1%

Maximum DC Output Current: (1.70 x E

Line

x I

Line

x Power Factor) / VDC

Maximum Short Circuit Current: 100KA

Output Voltage Resolution: 0.5V

Output Voltage Regulation: Less than 5% for +/- 100% current step change

Voltage Regulator Response: 100 rad/sec.

VAR/Power Factor Correction:

The user can select the maximum amount of SB3000 VAR correction. The SB3000
Power Module will always give the voltage regulator priority over the VAR function. If
the output of the SB3000 is less than its limit, it will attempt to produce VARs up to
the limit set by the user. Refer to Appendix B, section B.2.1.

SB3000 Power Module Current Ratings

1

SB3000 Part Number

Continuous

AC Input Current

(460VAC)

Continuous

DC Output Current

(800VDC)

5 Minute

AC Input and DC Output

Overload

2

850021 – 21xxx, 31xxx

445A (rms)

445A DC

534A (rms)

850021 – 22xxx, 32xxx

890A (rms)

890A DC

972A (rms)

850021 – 23xxx, 33xxx

1,335A (rms)

1,335A DC

1,457A (rms)

1. At 460 VAC Input/800 VDC Output/4 kHz Carrier Frequency. For use with SA3000 Power Modules operating at a 2 kHz carrier

frequency.

2. With a 25% duty cycle