Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual
Page 20

20 XM ControlNet Adapter
Publication
ICM-IN001B-EN-P - March 2013
Environmental Specifications
Attribute
Value
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):
-20…70 °C (-4…158 °F)
Non-Operating Temperature
IEC 60068-2-1 (Test Ab, Unpackaged
Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged
Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged
Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Surrounding Air Temperature, Maximum
70 °C (158 °F)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
15 g
Nonoperating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
20 g
Emissions
CISPR 11 (IEC 61000-6-4):
Class A
ESD Immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges