Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual
Page 21

XM ControlNet Adapter 21
Publication
ICM-IN001B-EN-P - March 2013
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV
line-earth(CM) on power ports
±2 kV line-earth(CM) on communications
ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
Certifications
(when product is marked)
Certifications
(1)
Description
c-UL-us
UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File
E194810.
CE
European Union 2004/108/EC EMC Directive, compliant
with:
• EN 61326-1; Meas./Control/Lab., Industrial
Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8,
Zone A & B)
Environmental Specifications
Attribute