TACHOMETER FEEDBACK KIT
Figure 6 - Tachometer Feedback Kit Mounted on Regulator Module
JUMPER J2
JUMPER J1
Figure 7 - Jumpers J1, J2
10. Disconnect lead 45 at contactor.
11. FlexPak Plus only - Install terminal block S1
between existing terminals 53 and 45. Add marking
tag S2 to top of existing terminal 45. Disconnect lead
45 at terminal block and remove this lead totally from
controller.
MinPak Plus only - Install terminal blocks S1 and
45ĆS2 between existing terminal blocks A2 and F1.
Reconnect lead 45 to terminal block 45.
12. Connect lead S1 to contactor. Lead must be routed
under terminal board mounting bracket. See figure 8.
FWD.
REG. PC
Figure 8 - Series FieldTerminal Connection
13. Cut jumper J9 on Regulator Printed Circuit Module.
14. Remount fuse/circuit breaker mounting plate to
auxiliary chassis using existing three screws.
15. Tighten all connectors that may have loosened
during kit installation
16. Close faceplate and tighten screws.
See figures 9 and 10 for an installed reversing kit
schematic and a typical bidirectional control scheme.