Interconnecting Terminal Base Units
Follow the steps below to install another terminal base unit.
1. Position the terminal base on the 35 x 7.5mm DIN rail (A).
2. Make certain the side connector (B) is fully retracted into the base
unit.
3. Slide the terminal base unit over tight against the neighboring terminal
base. Make sure the hook on the terminal base slides under the edge
of the terminal base unit.
4. Press down on the terminal base unit to lock the terminal base on the
DIN rail. If the terminal base does not lock into place, use a
screwdriver or similar device to open the locking tab, press down on
the terminal base until flush with the DIN rail and release the locking
tab to lock the base in place.
5. Gently push the side connector into the side of the neighboring
terminal base to complete the backplane connection.
IMPORTANT
Terminal base units are mounted left to right on the DIN rail.