North american hazardous location approval – Rockwell Automation 1440-TB-A XM-940 Dynamic Measurement Terminal Base User Manual
Page 5
 
XM-940 Dynamic Measurement Terminal Base 5
Publication
GMSI10-IN020C-EN-P - October 2013
North American Hazardous Location Approval
The following information applies when 
operating this equipment in hazardous 
locations.
Informations sur l’utilisation de cet 
équipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for 
use in Class I Division 2 Groups A, B, C, D, Hazardous 
Locations and nonhazardous locations only. Each product is 
supplied with markings on the rating nameplate indicating 
the hazardous location temperature code. When 
combining products within a system, the most adverse 
temperature code (lowest "T" number) may be used to help 
determine the overall temperature code of the system. 
Combinations of equipment in your system are subject to 
investigation by the local Authority Having Jurisdiction at 
the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu'à une utilisation en environnements de 
Classe I Division 2 Groupes A, B, C, D dangereux et non 
dangereux. Chaque produit est livré avec des marquages sur 
sa plaque d'identification qui indiquent le code de 
température pour les environnements dangereux. Lorsque 
plusieurs produits sont combinés dans un système, le code de 
température le plus défavorable (code de température le plus 
faible) peut être utilisé pour déterminer le code de 
température global du système. Les combinaisons 
d'équipements dans le système sont sujettes à inspection par 
les autorités locales qualifiées au moment de l'installation.
WARNING
EXPLOSION HAZARD -
• Do not disconnect equipment unless
power has been removed or the 
area is known to be nonhazardous. 
• Secure any external connections
that mate to this equipment by 
using screws, sliding latches, 
threaded connectors, or other 
means provided with this product.
• Substitution of components may
impair suitability for Class I, 
Division 2.
• If this product contains batteries,
they must only be changed in an 
area known to be nonhazardous.
AVERTISSEMENT
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer
que l'environnement est classé 
non dangereux avant de 
débrancher l'équipement.
• Couper le courant ou s'assurer
que l'environnement est classé 
non dangereux avant de 
débrancher les connecteurs. Fixer 
tous les connecteurs externes 
reliés à cet équipement à l'aide 
de vis, loquets coulissants, 
connecteurs filetés ou autres 
moyens fournis avec ce produit.
• La substitution de composants
peut rendre cet équipement 
inadapté à une utilisation en 
environnement de Classe I, 
Division 2.
• S'assurer que l'environnement est
classé non dangereux avant de 
changer les piles.