Dynamic Braking Kit for FlexPak Plus and MinPak Plus DC Drives

Step 6. For non-regenerative FlexPak Plus DC drives with a Reversing Contactor: Connect the dynamic

braking resistor between the corresponding normally closed (

NC

) contacts on the forward contactor

and the reversing contactor. For example, connect the resistor between terminal 8 on the forward
contactor and terminal 8 on the reverse contactor. This places the resistor across the motor’s
armature (A1 and A2) when both contactors are de-energized. Refer to figures 3 and 4.

Figure 2 – Dynamic Braking Resistor Schematic for Regenerative Drives

and Non-Regenerative Drives Without a Reversing Contactor

A1 (+)

Forward

Contactor

Forward

Contactor

A2 (–)

47

Forward

Contactor

Dynamic Braking

Resistor

Forward

Contactor

DB 1

DB 2

DC

Motor

45/52

Armature