6

Dynamic Braking Kit for FlexPak Plus and MinPak Plus DC Drives

Step 7. If a reversing contactor is installed, make sure jumper J9 is removed from the Regulator board (near

the top of board). See the FlexPak Plus DC drive instruction manual for jumper location.

Step 8. Verify the wiring of the Dynamic Braking resistor and that all connectors are securely fastened.

Step 9. Reattach the cover to the drive.

Step 10. Apply power and test the braking capability of the drive.

This completes installation of the Dynamic Braking kit for FlexPak Plus DC drives.

Figure 4 – Dynamic Braking Resistor Schematic for Non-Regenerative Drives with a Reversing Contactor

!

ATTENTION: If a reversing contactor is installed, ensure jumper J9 is removed from the
Regulator board (near the top of board). Failure to observe this precaution could result in
damage to, or destruction of, the equipment.