Rockwell Automation T8110B Trusted Industrial Control System User Manual
Sds-8110 trusted, Industrial control system trusted, Tmr processor-t8110b
 
SDS-8110 
Trusted
TM
Industrial Control System
Trusted
TM
TMR Processor-T8110B
Issue 7 Dec 2006
FRONT PANEL
DESCRIPTION
 
Trusted
TM
TMR Processors contain and
execute the operating and application software 
programs in a triple redundant, fault tolerant 
controller system.. 
The fault tolerant design contains six fault 
containment regions. The three synchronized 
processor fault containment regions each 
contain a 600 series microprocessor, its 
memory, voter, and associated circuits. 
The non-volatile memory is used to store the 
configuration and application programs for the 
system. 
Each processor has an independent 
power supply fed from the dual-
redundant 24Vdc power supply of the 
Trusted
TM
Controller chassis backplane.
The processor power supplies provide 
short circuit protection and regulated 
power to the module electronics. 
The processors operate concurrently to 
achieve triple modular redundancy and 
fault tolerance. By providing 2-out-of-3 
hardware voting on every inter-
processor exchange and memory data 
retrieval, uncompromised fault detection 
and error-free operation are assured. 
Trusted
TM
TMR
Processors
communicate with other modules via a 
backplane mounted, triplicated Inter-
Module Bus. Additionally, interface 
modules 
are
used
to
support
communication with I/O sub-systems 
and other equipment. 
Module
faults
are
automatically
detected, time-stamped, and stored for 
historical review. Transient faults, once 
they 
are
recorded,
are
cleared
automatically without nuisance alarming. 
Permanent faults in a processor are 
annunciated on the front panel of the 
module, without disturbing on-going 
processing in the two remaining 
processors. 
When
a
failed
Trusted
TM
TMR
Processor is replaced, the replacement 
module is automatically initialized 
without external loaders or other 
equipment. 
Application programs are developed 
using the full suite of IEC 1131-3 
languages. The user can load, run, 
stop, 
single-step
or
delete
the
application program. A front panel 
maintenance enable keyswitch allows 
the download of application programs. 
FEATURES
Triple modular 
redundant, fault 
tolerant 3-2-0 
operation 
Two-out-of-three 
voting on internal 
operations 
Automatic fault 
handling without 
nuisance alarming 
Trusted
TM
Operating
System kernel (IEC 
61508 SIL3) 
Time-stamped fault 
historian 
Module replacement 
without program 
down-loading 
Non-volatile 
memory for 
program storage 
Full suite of IEC 
1131-3 languages 
Multiple process 
program execution 
TÜV certified for 
safety, SIL3