Triguard SC300E MAO04NND Analogue Output Module
Figure 2-2 Analogue output section - Schematic block diagram
Analogue outputs
Five test-sockets are provided for monitoring the output lines: one common terminal via 2.2k 
ohm to the +24V field supply, and the other four via 10k ohm to the current-determining 
resistors on the termination card. These resistors are 250 ohm, so 20mA of loop-current 
corresponds to 5V across them. 
The four analogue voltage outputs use 12-bit DACs to produce +0.4V to –6V with respect to 
field +24V common, applied across resistors on the termination card. The outputs from the 
three channels go through a voting scheme using FETs to select the middle-value output, so 
that if one channel fails high or low, one of the other two outputs will be selected (see Figure 2-
2). 
The resultant current of 0 to 22mA determined by the voltage and resistor is fed to the field 
device, then returns to the supply negative via the termination card.